Twelve year service · NFPA 10 §8.3

Hydrostatic testing at twelve years

The cylinder itself is pressure tested. This is the interval that decides whether a unit stays in service or is replaced.

Hamilton Fire Protection12 YEAR

Hydrostatic testing

NFPA 10 §8.3
EVERY 12 YEARS
Performed byLicensed technician
Price per unitQuoted per site
What the service includes

The cylinder is tested, not just the contents

StepWhat we check or replace
Strip and inspectValve removed, cylinder emptied and examined inside and out.
Pressure testTested to the test pressure stamped on the cylinder shell.
Expansion checkPermanent expansion measured against the allowable limit.
Condemn or returnFailed shells are condemned and removed from service, not repaired.
Test recordTest date and our mark applied to the cylinder as the permanent record.
ABC dry chemical extinguishers on the Hamilton Fire Protection bench during service
Who performs it

Performed at a licensed facility. The cylinder is tested to the pressure stamped on its own shell, not a generic figure.

Technician licenseType B, portables only
If it lapses

What an inspector sees

Past twelve years without a test the unit is out of service, whatever the tag says. This is the interval most often missed, because the date lives on the cylinder stamp rather than the tag.

Read the compliance guide
Applies to
Dry chemical, stored pressure
12 YEARS
Carbon dioxide cylinders
5 YEARS
Water and wet chemical
5 YEARS
Date source
CYLINDER STAMP