Reference document · NFPA 10

The extinguisher compliance guide

Written for the person who has to answer the fire marshal, not for a technician. Every interval, who is allowed to perform it, and what gets written up when it slips.

Standard
NFPA 10
Written against
2022 edition

Your authority having jurisdiction may enforce an earlier edition. Every interval in this guide is unchanged from the 2018 edition, so nothing here turns on which one applies to your building.

Take it with you

The Texas Fire Extinguisher Compliance Guide

The full reference, laid out to print. Who regulates extinguisher work in Texas, how to verify a service company is licensed, every interval by extinguisher type, how to read a tag, and what to hand an inspector. Built to sit in the binder with your other compliance records.

PDF · 15 pages · 0.8 MBNo email required
Download the guidehamilton-texas-fire-extinguisher-compliance-guide.pdf
01 · What gets checked

What a fire marshal actually looks at

Most findings are not equipment failures. They are paperwork failures. The inspector walks the building, reads tags, and counts. Four things decide the outcome, and all four are visible from arm's length.

A current tag on every unit. A monthly check record on the back of that tag. The unit mounted at the right height with clear access. And enough units that no one has to walk further than the hazard class allows.

The four findings, in the order they are written
  1. 01
    Expired or missing tag
    Read from arm’s length. The punch date is dated evidence, so there is nothing to argue.
  2. 02
    No monthly check record
    The back of the tag is blank or stops several months ago.
  3. 03
    Blocked or unmounted unit
    Sitting on the floor, behind stock, or moved during a fit-out and never remounted.
  4. 04
    Too few units for the hazard
    Travel distance measured from the furthest point of the space to the nearest unit.
02 · The intervals

Every interval, and who may perform it

One of these is yours. The rest require a technician licensed by the Texas State Fire Marshal.

IntervalServicePerformed byCitation
MONTHLYVisual checkYour staff§7.2
ANNUALInspection and taggingLicensed technician§7.2
6 YEARInternal maintenanceLicensed technician§7.3
12 YEARHydrostatic testLicensed technician§8.3
03 · Your monthly check

The one you perform yourself

No license is required for the monthly visual check, and no tools. It takes about thirty seconds per unit. Initial and date the back of the tag when you are done, because the record is the part that gets inspected.

01
In place
Unit is on its bracket, in the location marked on your plan.
02
Unobstructed
Nothing stacked in front of it, signage visible from the approach.
03
Gauge in range
Needle sits in the operable band, not left or right of it.
04
Seal and pin intact
Tamper seal unbroken, pin present and free.
05
No visible damage
No dents, corrosion, or split hose. Nozzle clear.
06
Initial the tag
Sign and date the back. This is the record that gets read.
04 · Placement

Mounting height and travel distance

A correctly serviced unit in the wrong place is still a finding. These are the figures an inspector measures.

Units 40 lb and under, top of unit
MAX 5 FT
Units over 40 lb, top of unit
MAX 3.5 FT
Clearance from the floor
MIN 4 IN
Travel distance, Class A hazard
MAX 75 FT
Travel distance, Class B hazard
MAX 30 TO 50 FT
Class K, cooking appliance
MAX 30 FT

Check a floorplate against the travel limit

05 · Records

What to keep, and for how long

The tag is the primary record and it lives on the unit. Everything else lives in your file, and the file is what an insurance carrier asks for after a claim rather than during an inspection.

The tag answers the inspector. The file answers the carrier. Keep both, because the two questions arrive at different times and only one of them is scheduled.

06 · Division of work

What you do, what we do

Your staff
  • The monthly visual check on every unit
  • Initial and date the back of the tag
  • Tell us when a unit is used, moved, or damaged
  • Keep the service records in your file
Hamilton
  • The annual inspection and the punched tag
  • Recharge after any discharge
  • Six year internal maintenance
  • Twelve year hydrostatic testing
  • A written service record for your file

This guide summarises NFPA 10 and Texas administrative rules for facilities managers. It is not the standard itself. Verify against the edition your authority having jurisdiction enforces.

Book the interval you have missed

Send the site address and unit count. If you are working against an inspection date, say so and it moves up the list.